r0039[0...2]
CO: Energy display / Energy display
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
- [kWh]
Max:
- [kWh]
Factory setting:
- [kWh]
Description:
Displays the energy values at the output terminals of the power unit.
Recommendation:
r0042 should be used as process energy display. R0039 supplies as Bico source floating point values in Ws.
Index:
[0] = Energy balance (sum)
[1] = Energy drawn
[2] = Energy fed back
Dependency:
See also: p0040
Note
For index 0:
Difference between the energy drawn and energy that is fed back.
p0040
Reset energy consumption display / Energy usage reset
Access level: 3
Calculated: -
Data type: Unsigned8
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
0
Description:
Setting to reset the display in r0039 and r0041.
Procedure:
Set p0040 = 0 --> 1
The displays are reset and the parameter is automatically set to zero.
Dependency:
See also: r0039
Note
When this display is reset (p0040), then the process energy display (r0042) is also reset.
r0041
Energy consumption saved / Energy cons saved
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
- [kWh]
Max:
- [kWh]
Factory setting:
- [kWh]
Description:
Displays the saved energy referred to 100 operating hours.
Dependency:
See also: p0040
Note
This display is used for a fluid-flow machine.
The flow characteristic is entered into p3320 ... p3329.
For an operating time of below 100 hours, the display is interpolated up to 100 hours.
r0042[0...2]
CO: Process energy display / Proc energy disp
Access level: 2
Calculated: -
Data type: Integer32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
- [Wh]
Max:
- [Wh]
Factory setting:
- [Wh]
Parameters
7.2 Parameter list
SINAMICS G120X converter
480
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......