r0025
CO: Output voltage smoothed / Output voltage
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2001
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 5730, 6300,
6799
Min:
- [Vrms]
Max:
- [Vrms]
Factory setting:
- [Vrms]
Description:
Displays the smoothed output voltage of the power unit.
Dependency:
See also: r0072
Note
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The output voltage is available smoothed (r0025) and unsmoothed (r0072).
r0026
CO: DC link voltage smoothed / DC link voltage
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2001
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 6799
Min:
- [V]
Max:
- [V]
Factory setting:
- [V]
Description:
Displays the smoothed actual value of the DC link voltage.
Dependency:
See also: r0070
NOTICE
When measuring a DC link voltage < 200 V, for the Power Module (e.g. PM240) a valid measured value is not supplied.
In this case, when an external 24 V power supply is connected, a value of approx. 24 V is displayed in the display
parameter.
Note
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
r0026 sets itself to the lower value of the pulsating DC link voltage.
r0027
CO: Absolute actual current smoothed / Motor current
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2002
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 5730, 6799,
8850, 8950
Min:
- [Arms]
Max:
- [Arms]
Factory setting:
- [Arms]
Description:
Displays the smoothed absolute actual current value.
Dependency:
See also: r0068
NOTICE
This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the unsmoothed
value should be used.
Note
Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The absolute current actual value is available smoothed (r0027) and unsmoothed (r0068).
Parameters
7.2 Parameter list
SINAMICS G120X converter
474
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......