Article number
Converter frame
size
Rated power (kW)
Sine-wave filter
400 V converters
FSD
18.5 … 22
6SL3202-0AE24-6SA0
30
6SL3202-0AE26-2SA0
37
6SL3202-0AE28-8SA0
FSE
45
55
6SL3202-0AE31-5SA0
FSF
75
90
6SL3202-0AE31-8SA0
110 … 132
6SL3000-2CE32-3AA0
FSG
1)
160
6SL3000-2CE32-8AA0
200
6SL3000-2CE33-3AA0
250
6SL3000-2CE34-1AA0
1)
For converter FSG with sine-wave filter, operation is only permissible in the vector control mode. It is
not permissible for U/f mode to be used.
2.6.6
dv/dt filter plus VPL
Note
dv/dt filters plus VPL are available as optional components for converters FSD to FSJ only.
A combination of dv/dt filter and a voltage peak limiter (VPL) - dv/dt filter plus VPL - are available
to suppress voltage peaks and enable longer motor cables to be connected.
Maximum permissible motor cable length (Page 82)
When using the dv/dt filter plus VPL, observe the following restrictions:
● The maximum output frequency is 150 Hz.
● The maximum pulse frequency is 4 kHz.
NOTICE
Damage to the dv/dt filter plus VPL if it is not activated during commissioning
The dv/dt filter plus VPL may be damaged if it is not activated during commissioning.
● Activate the dv/dt filter plus VPL during commissioning via parameter p0230.
● Activate the dv/dt filter plus VPL during commissioning according to the electric
specifications.
Description
2.6 Optional components
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
39
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......