You have the following options for integrating SINAMICS G120 frequency converters into
EtherNet/IP:
● You use the SINAMICS profile
● You use the ODVA AC/DC drive profile
● You define the assemblies for the process data using the objects that are supported by the
converter
6.3.4.1
Configuring communication via EtherNet/IP
Precondition
You have connected the converter with a commissioning tool e.g. an operator panel
Basic settings
Make the following settings in order to communicate with a higher-level control via EtherNet/IP:
Procedure
1. Set the following parameters:
– p2030 = 10: Protocol selection Ethernet/IP
If p2030 = 10, the following parameters apply for EtherNet/IP, even if the parameter
names seem to indicate PROFINET.
– p8921 = IP address
You can find the currently valid address in r8931.
– p8923 = subnet mask
You can find the currently valid subnet mask in r8933.
– p8922 = default gateway
You can find the currently valid default gateway in r8932.
– p8920 = name of station
– p8925 = 2: Save and activate interface configuration
2. Switch off the converter power supply.
3. Wait until all LEDs on the converter are dark.
4. Switch on the converter power supply again.
You have now configured the converter for communication via EtherNet/IP.
❒
Communication settings
You set the communication using parameter p8980. You have the following options
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
225
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......