Electrical installation
4.8 Signal connections
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
71
4.7.1
230 VAC auxiliary supply
The fuse must not exceed 16 A.
The connection is protected inside the cabinet with a 3 A fuse.
Connecting
●
On terminal block -X40, remove the jumpers between terminals 1 and 2 as well as 3 and 4.
●
Connect the external 230 V AC supply to terminals 2 (L1) and 4 (N).
Maximum connectable cross-section: 4 mm²
4.7.2
24 VDC auxiliary supply
The fuse must not exceed 10 A.
The power requirement is 2 A.
Connecting
Connect the external 24 VDC supply to terminals 1 (P 24 V) and 2 (M
ext
) of terminal block –X9.
Maximum connectable cross-section: 1.5 mm²
4.8
Signal connections
4.8.1
CU230P-2 Control Unit
One of the following CU230P-2 Control Units that handles the communication and open-
loop/closed-loop control functions is provided as closed-loop module:
Control Unit
CU230P-2 PN
CU230P-2 DP
CU230P-2 HVAC
CU230P-2 CAN
Fieldbus interface
PROFINET IO
PROFIBUS DP
RS485 (USS,
Modbus RTU,
BACnet MS/TP, P1)
CANopen
Digital inputs
6
6
6
6
Analog inputs
4
4
4
4
Digital outputs
3
3
3
3
Analog outputs
2
2
2
2
Motor temperature sensor
connection
1
1
1
1
Option short codes
K96
K97
K98
K99
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......