Functions
7.7 Application-specific functions
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
401
Note
If you use a temperature sensor as the input for the technology controller, you have to
modify the scaling of the analog input.
•
Scaling example for LG-Ni1000:
0° C (p0757[x]) = 0% (p0758[x]); 100° C (p0759[x]) = 100% (p0760[x])
•
Scaling example for Pt1000:
0° C (p0757[x]) = 0% (p0758[x]); 80 % C (p0759[x]) = 100% (p0760[x])
Please refer to the parameter list as well as the 2252 and 2270 function block diagrams for
further details.
7.7.13
Essential service mode
In the Essential Service Mode (ESM), the motor must operate for as long as possible, for
example in the case of a fire, to keep the evacuation routes open by extracting smoke.
Contrary to normal operation, when faults develop, the inverter does not shut down, but
responds as follows
●
Faults that do not immediately result in the destruction of the inverter or the motor:
The inverter ignores these faults, and continues to operate in the "essential service
mode".
●
Faults that cannot be ignored and require a restart:
the inverter automatically restarts and uses this function to try to acknowledge the
pending faults.
●
Faults, which also cannot be resolved after a restart:
In this case, there is the option of activating the bypass function and to directly operate
the motor from the line supply.
WARNING
Danger to life due to fire in essential service mode
In essential service mode, exceptionally high temperatures, including an open fire, as well
as emissions of light, noise, particles, gases, etc. can occur inside and outside the inverter.
Fire and smoke can cause death, severe injury or material damage.
•
Use essential service mode only when the named restrictions are satisfied.
Note
Loss of warranty for an inverter operated in the essential service mode
If you activate the essential service mode, then all warranty claims are null and void with
reference to the inverter.
The essential service mode is an exceptional state, and is not suitable for continuous
operation.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......