Functions
7.7 Application-specific functions
Inverter cabinet units
378
Operating Instructions, 12/2014, A5E32923362A
7.7.2
Energy-saving display
Background
Conventionally-controlled fluid flow machines control the flow rate using valves or throttles.
In so doing, the drive operates constantly at the rated speed. The efficiency of the system
decreases if the flow rate is reduced using valves or throttles. The efficiency is the lowest
when valves or throttles are completely closed. Further, undesirable effects can occur, e.g.
the formation of vapor bubbles in liquids (cavitation) or the temperature rise of the medium
being pumped increases.
The inverter controls the flow rate or the pressure by varying the speed of the fluid flow
machine. As a consequence, over its complete operating range, a fluid-flow machine
operates close to its maximum efficiency – and especially in partial load operation, uses less
energy than for valve and throttle-based closed-loop control.
Function
The energy-saving display calculates the energy saved when operating fluid-flow machines,
e.g. centrifugal pumps, fans, radial and axial compressors. The energy-saving display
compares inverter operation with direct line operation and throttle control.
The inverter indicates the energy saved in parameter r0041 in kWh, referred to the last 100
operating hours.
For less than 100 operating hours, the inverter interpolates the energy saving to 100
operating hours.
The inverter calculates the energy-saving based on the operating characteristic that has
been saved.
Table 7- 26 Operating characteristic set in the factory
Point 1
Point 2
Point 3
Point 4
Point 5
Power
p3320 = 25%
p3322 = 50%
p3324 = 77%
p3326 = 92%
p3328 = 100%
Speed
p3321 = 0%
p3323 = 25%
p3325 = 50%
p3327 = 75%
p3329 = 100%
If you require a precise value for the energy saving, then you must adapt the operating
characteristic set in the factory.
Additional parameters for the energy consumption display:
r0039[0]: Energy consumption since the last reset.
r0039[1]: Energy drawn since the last reset.
r0039[2]: Energy fed back since the last reset.
p0040: Parameter to reset parameters r0039 and r0041.
r0041: Displays the saved energy since the last reset, referred to the operating
characteristic, defined by parameters p3320 …p3329.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......