Functions
7.6 Protection functions
Inverter cabinet units
368
Operating Instructions, 12/2014, A5E32923362A
7.6.3
Protecting the motor by calculating the motor temperature
The temperature calculation is only possible in the vector control mode (p1300 = 20) and
functions by calculating a thermal motor model.
Table 7- 23 Parameters for temperature acquisition without using a temperature sensor
Parameter
Description
p0621= 1
Motor-temperature acquisition after restart
0: No temperature measurement (factory setting)
1: Temperature measurement after the motor is switched on for the first time
2: Temperature measurement each time that the motor is switched on
p0622
Magnetization time of the motor for temperature measurement after starting
(set au-
tomatically as the result of motor data identification)
p0625
Ambient motor temperature
Enter the ambient motor temperature in °C at the instant that the motor data is ac-
quired (factory setting: 20° C).
The difference between the motor temperature and motor environment (p0625) must
lie within a tolerance range of approx. ± 5° C.
7.6.4
Overcurrent protection
During vector control, the motor current remains within the torque limits set there.
During V/f control, the maximum current controller (I-max controller) protects the motor and
inverter against overload by limiting the output current.
I-max controller operation
If an overload situation occurs, the speed and stator voltage of the motor are reduced until
the current is within the permissible range. If the motor is in regenerative mode, i.e. it is
being driven by the connected machine, the I-max controller increases the speed and stator
voltage of the motor to reduce the current.
Note
The inverter load is only reduced if the motor torque decreases at lower speeds, e.g. for
fans.
In the regenerative mode, the current only decreases if the torque decreases at a higher
speed.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......