Functions
7.2 Inverter control
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
339
7.2.3
Two-wire control, method 2
You switch the motor on and off using a control command (ON/OFF1) and at the same time
select clockwise motor rotation. You also use the other control command to switch the motor
on and off, but in this case you select counter-clockwise rotation for the motor.
The inverter only accepts a new control command when the motor is at a standstill.
Figure 7-3
Two-wire control, method 2
Table 7- 3
Function table
ON/OFF1
clockwise
rotation
ON/OFF1
counter-
clockwise
rotation
Function
0
0
OFF1: The motor stops.
1
0
ON: Clockwise motor rotation.
0
1
ON: Counter-clockwise motor rotation.
1
1
ON: The motor direction of rotation is based on the signal that
assumes status "1" first.
Parameter
Description
p0015 = 17
Macro drive unit
Controlling the motor using the
digital inputs of the inverter:
DI 0
DI 1
ON/OFF1 clock-
wise rotation
ON/OFF1 coun-
ter-clockwise
rotation
Advanced setting
Interconnecting control commands with digital inputs of your choice (DI x).
p3330[0 … n] = 722.x BI: 2/3 wire control command 1 (ON/OFF1 clockwise rotation)
p3331[0 … n] = 722.x BI: 2/3 wire control command 2 (ON/OFF1 counter-clockwise rotation)
Example
p3331[0 … n] = 722.0 DI 0: ON/OFF1 counter-clockwise rotation
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......