Operation
6.9 Communication over CANopen
Inverter cabinet units
288
Operating Instructions, 12/2014, A5E32923362A
OD index
(hex)
Sub-
index
(hex)
Name of the object
SINAMICS
parameters
Trans-
mission
Data
type
Default
setting
Can be
read/
written
Velocity mode
6042
vl target velocity
r8792
SDO/
PDO
I16
–
r/w
6043
vl velocity demand
r1170
SDO/
PDO
I16
–
r
6044
vl velocity actual value
r0063
SDO/
PDO
I16
–
r
6046
0
vl velocity min./max. amount
SDO
U8
–
r
1
vl velocity min. amount
p1080
SDO
U32
–
r/w
2
vl velocity max. amount
p1082
SDO
U32
–
r/w
6048
0
vl velocity acceleration
SDO
U8
–
r
1
Delta speed
p1082
SDO
U32
–
r/w
2
Delta time
p1120
SDO
U16
–
r/w
1)
Without ramp-function generator
2)
With ramp-function generator
3)
The inverter processes the objects of profile velocity mode and profile torque mode. But they cannot be set nor selected
in inverters.
6.9.3
Integrating the converter into CANopen
Commissioning
Precondition
•
STARTER ≥ version 4.2, is installed on the computer
used to commission the system.
•
The inverter is connected to a CANopen master.
•
The EDS (Electronic Data Sheet)
http://support.automation.siemens.com/WW/view/en/4
)is installed on your CANopen master.
•
In the basic commissioning you have set the inverter
interfaces to the CANopen fieldbus.
This means that the following signals in the inverter are
interconnected corresponding to the Predefined
Connection Sets:
–
Speed setpoint and control word
–
Actual speed value and status word
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......