Operation
6.8 Communication via RS485
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
231
6.8.3.1
Basic settings for communication
You set the bus address of the inverter using the
address switches on the Control Unit, using pa-
rameter p2021 or in STARTER.
Using parameter p2021 (factory setting: 1) or using
STARTER, you can only set the address, if all
address switches are set to "OFF" (0).
Valid address range: 1 … 247
If you have specified a valid address using the
address switches, this address will always be the
one that takes effect, and parameter p2021
(factory setting: 1) will not be able to be changed.
The positions of the address switches are de-
scribed in Section: CU230P-2 HVAC Control Unit
(option K98) (Page 87).
Procedure
To change the bus address, proceed as follows:
1.
Set the address using one of the subsequently listed options:
–
Using the address switches
–
With the IOP using p2021
–
In STARTER using screen form "Control Unit/Communication/Fieldbus", or using the
expert list in parameter p2021.
2.
Switch on the inverter power supply and, if available, the 24 V power supply for the
Control Unit.
3.
Switch on the voltages again after all LEDs at the inverter have gone dark.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......