Operation
6.8 Communication via RS485
Inverter cabinet units
220
Operating Instructions, 12/2014, A5E32923362A
6.8.2.2
Telegram structure
Overview
A USS telegram comprises a series of elements with a defined sequence. Each element
contains 11 bits.
Figure 6-13 Structure of a USS telegram
Telegram part
Description
Start delay / re-
sponse delay
There is always a start and/or response delay between two telegrams (see
alsoTime-out and other errors (Page 227)).
STX
An ASCII character (02 hex) indicates the beginning of the message.
LGE
The telegram length "LGE" is calculated as follows:
LGE = user data (n bytes) + ADR (1 byte) + BCC (1 byte)
ADR
•
Bit 7 = 0: Normal data exchange.
Bit 7 = 1: To transfer telegrams that require a net data structure different
from the device profile.
•
Bit 6 = 0: Normal data exchange.
Bit 6 = 1: Testing the bus connection: The inverter returns the telegram un-
changed to the master.
•
Bit 5 = 0: Normal data exchange.
(Bit 5 = 1: Not supported in the inverter.)
•
Bits 0 ... 4: Address of the inverter.
Net data
See Section User data range of the USS telegram (Page 221).
BCC
Checksum (exclusive or) across all telegram bytes – with the exception of
BCC.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......