6.7.2
What do you need for communication via Ethernet/IP?
Check the communication settings using the following questions. If you answer "Yes" to the
questions, you have correctly set the communication settings and can control the inverter via
the fieldbus.
●
Is the inverter correctly connected to the EtherNet/IP?
●
Is the EDS file (Page 207) installed in your control system?
●
Have the bus interface and IP address been correctly set?
●
Have the signals that the inverter and the control system exchange been correctly
interconnected?
6.7.3
Communication settings for Ethernet/IP
General communication settings
In order to be able to communicate with a higher-level controller via EtherNet/IP, you must
set parameter p2030 = 10.
Further, you must set the following data:
•
IP address
in p8921
currently valid value in r8931
•
Subnet mask
in p8923
currently valid value in r8933
•
Default gateway
in p8922
currently valid value in r8932
•
Name of station
in p8920
currently valid value in r8930
These parameters apply if p2030 = 10 is set, for EtherNet/IP, even if the parameter name
indicates PROFINET.
Modified addresses only become effective if you switch-off the inverter and switch it on
again; this includes any external 24 V supply that is being used.
Additional settings for communication via EtherNet/IP
Setting the communication profile
The inverter has two communication profiles
●
p8980 = 0: SINAMICS profile (factory setting)
A drive profile defined by Siemens for EtherNet/IP based on PROFIdrive
●
p8980 = 1: ODVA AC/DC drive profile
A drive profile defined by the ODVA organization
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......