Status word 1 (ZSW1)
Status word 1 (bits 0 … 10 in accordance with PROFIdrive profile and VIK/NAMUR, bits 11
… 15 specific to the inverter). See also function diagram 2451/2452.
Bit Significance
Comments
Signal intercon-
nection in the
inverter
Telegram 20
All other tele-
grams
0
1 = Ready to start
The power supply is switched on; electronics initialized;
pulses locked.
p2080[0] =
r0899.0
1
1 = Ready
The motor is switched on (ON/OFF1 = 1), no fault is active.
With the command "Enable operation" (STW1.3), the invert-
er switches on the motor.
p2080[1] =
r0899.1
2
1 = Operation enabled
The motor follows the setpoint. See control word 1, bit 3.
p2080[2] =
r0899.2
3
1 = Fault active
The inverter has a fault. Acknowledge fault using STW1.7.
p2080[3] =
r2139.3
4
1 = OFF2 inactive
Coast down to standstill is not active.
p2080[4] =
r0899.4
5
1 = OFF3 inactive
Quick stop is not active.
p2080[5] =
r0899.5
6
1 = Closing lockout active
It is only possible to switch on the motor after an OFF1
followed by ON.
p2080[6] =
r0899.6
7
1 = Alarm active
The motor remains switched on; no acknowledgement is
necessary.
p2080[7] =
r2139.7
8
1 = Speed deviation within the
tolerance range
Setpoint / actual value deviation within the tolerance range. p2080[8] =
r2197.7
9
1 = Master control requested
The automation system is requested to accept the inverter
control.
p2080[9] =
r0899.9
10 1 = Comparison speed reached or
exceeded
Speed is greater than or equal to the corresponding maxi-
mum speed.
p2080[10] =
r2199.1
11 0 = I, M or P limit reached
Comparison value for current, torque or power has been
reached or exceeded.
p2080[11] =
r1407.7
12 ---
1)
1 = Holding
brake open
Signal to open and close a motor holding brake.
p2080[12] =
r0899.12
13 0 = Alarm, motor overtemperature --
p2080[13] =
r2135.14
14 1 = Motor rotates clockwise
Internal inverter actual value > 0
p2080[14] =
r2197.3
0 = Motor rotates counterclock-
wise
Internal inverter actual value < 0
15 1 = CDS dis-
play
0 = Alarm, in-
verter thermal
overload
p2080[15] =
r0836.0 /
r2135.15
1)
If you change over from another telegram to telegram 20, then the assignment of the previous telegram is kept.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......