Operation
6.5 PROFIdrive profile for PROFIBUS and PROFINET
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
189
Control word 1 (STW1)
Control word 1 (bits 0 … 10 in accordance with PROFIdrive profile and VIK/NAMUR, bits 11
… 15 specific to the inverter). See also function diagram 2441/2442.
Bit Significance
Explanation
Signal intercon-
nection in the
inverter
Telegram 20
All other tele-
grams
0
0 = OFF1
The motor brakes with the ramp-down time p1121 of the
ramp-function generator. The inverter switches off the motor
at standstill.
p0840[0] =
r2090.0
0
→ 1 = ON
The inverter goes into the "ready" state. If, in addition
bit 3 = 1, then the inverter switches on the motor.
1
0 = OFF2
Switch off the motor immediately, the motor then coasts
down to a standstill.
p0844[0] =
r2090.1
1 = No OFF2
The motor can be switched on (ON command).
2
0 = Quick stop (OFF3)
Quick stop: The motor brakes with the OFF3 ramp-down
time p1135 down to standstill.
p0848[0] =
r2090.2
1 = No quick stop (OFF3)
The motor can be switched on (ON command).
3
0 = Inhibit operation
Immediately switch-off the motor (cancel pulses).
p0852[0] =
r2090.3
1 = Enable operation
Switch-on the motor (pulses can be enabled).
4
0 = Disable RFG
The inverter immediately sets its ramp-function generator
output to 0.
p1140[0] =
r2090.4
1 = Do not disable RFG
The ramp-function generator can be enabled.
5
0 = Stop RFG
The output of the ramp-function generator stops at the actu-
al value.
p1141[0] =
r2090.5
1 = Enable RFG
The output of the ramp-function generator follows the set-
point.
6
0 = Inhibit setpoint
The inverter brakes the motor with the ramp-down time
p1121 of the ramp-function generator.
p1142[0] =
r2090.6
1 = Enable setpoint
The motor accelerates with the ramp-up time p1120 to the
setpoint.
7
0 → 1 = Acknowledge faults
Acknowledge fault. If the ON command is still active, the
inverter switches to the "closing lockout" state.
p2103[0] =
r2090.7
8, 9 Reserved
10 0 = No control via PLC
The inverter ignores the process data from the fieldbus.
p0854[0] =
r2090.10
1 = Control via PLC
Control via fieldbus, the inverter accepts the process data
from the fieldbus.
11 ---
1)
0 = Direction
reversal
Invert the setpoint in the inverter.
p1113[0] =
r2090.11
12 Reserved
13 ---
1)
1 = MOP up
Increase the setpoint saved in the motorized potentiometer. p1035[0] =
r2090.13
14 ---
1)
1 = MOP down Reduce the setpoint saved in the motorized potentiometer. p1036[0] =
r2090.14
15 CDS bit 0
Reserved
Changes over between settings for different operation inter-
faces (command data sets).
p0810 = r2090.15
1)
If you change over from another telegram to telegram 20, then the assignment of the previous telegram is kept.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......