Electrical installation
4.9 Other connections
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
121
4.9.12
Thermistor motor protection device (option L83/L84)
Description
This option includes the thermistor motor protection unit (with PTB approval) for PTC
thermistor sensors (PTC resistor type A) for warning and shutdown. The power supply for
the thermistor motor protection unit is provided inside the converter where the evaluation is
also performed.
Option L83 triggers the "external alarm 1" (A7850) if a fault occurs.
Option L84 triggers the "external fault 1" (F7860) if a fault occurs.
Connection
Table 4- 48 -B127/-B125 – connection for thermistor motor protection device
Equipment designation
Description of function
-B127: T1, T2
Thermistor motor protection (alarm)
-B125: T1, T2
Thermistor motor protection (shutdown)
The PTC thermistor sensors are connected directly to terminals T1 and T2 of the evaluation
unit.
Table 4- 49 Maximum cable length for the sensor circuit
Line cross-section in mm²
Line length in m
2.5
2 x 2800
1.5
2 x 1500
0.5
2 x 500
Diagnostics
Messages output during operation and in the event of faults (meaning of LEDs on -B125,
-B127) are described in the Operating Instructions in the customer DVD supplied with the
equipment.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......