![Siemens SINAMICS G120P Скачать руководство пользователя страница 113](http://html.mh-extra.com/html/siemens/sinamics-g120p/sinamics-g120p_operating-instructions-manual_378189113.webp)
Electrical installation
4.9 Other connections
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
113
4.9.8
Cabinet anti-condensation heating (option L55)
Description
The anti-condensation heating is used at low ambient temperatures and high levels of
humidity to prevent condensation forming.
A 100 W heating unit is installed with 400/600 mm cabinet panels, two heating units of 100
W each are installed with 800/1000 and 1200 mm cabinet panels. The power supply (110 to
230 VAC) must be provided externally and protected with a fuse of up to 16 A.
WARNING
Danger to life due to dangerous voltage when cabinet anti-condensation heating is used
When the cabinet anti-condensation heating is connected, dangerous voltages are present
in the cabinet unit even when the main circuit-breaker is open. Touching live parts can
result in death or severe injury.
•
Observe the general safety rules when working on the device.
CAUTION
Danger of injury through contact to hot surfaces on the cabinet anti-condensation heating
In operation, the cabinet anti-condensation heating can reach high temperatures, which can
cause burns if touched.
•
Allow the cabinet anti-condensation heating to cool down before starting any work.
•
Use the appropriate personnel protection equipment, e.g. gloves.
Note
Provide power supply
The supply voltage can be provided using a temperature control on the system to avoid
unnecessarily operating the anti-condensation heating for higher ambient temperatures.
Connecting up
Table 4- 39 Terminal block X240 – connection for cabinet anti-condensation heating
Terminal
Designation
Technical data
1
L1
110 to 230 VAC
Power supply
2
N
3
PE
Protective conductor
Max. connectable cross-section: 4 mm
2
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......