Adapt fieldbus configuration
6.2 PROFIdrive profile for PROFIBUS and PROFINET
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
99
Positioning status word 2 (POS_ZSW2)
Table 6- 11 POS_ZSW2 and interconnection with parameters in the converter
Bit Meaning
Comments
P No.
0 1 = Follow-up mode active
The converter is in the follow-up mode.
p2084[0] =
r2683.0
1 1 = Velocity limiting is active
The converter limits the velocity of the axis.
p2084[1] =
r2683.1
2 1 = Setpoint is stationary
During a positioning operation, the setpoint no longer
changes.
p2084[2] =
r2683.2
3 1 = Print index outside outer window
The discrepancy between the actual position and the
reference point was greater than permitted during flying
referencing.
p2084[3] =
r2684.3
4 1 = Axis traverses forwards
The axis traverses in the positive direction.
p2084[4] =
r2683.4
0 = Axis is stationary or traverses back-
wards
---
5 1 = Axis traverses backwards
The axis traverses in the negative direction.
p2084[5] =
r2683.5
0 = Axis is stationary or traverses forwards ---
6 1 = Software limit switch, minus actuated
The axis is outside the permitted traversing range.
p2084[6] =
r2683.6
7 1 = Software limit switch, plus actuated
p2084[7] =
r2683.7
8 1 = Position actual val
ue ≤ cam switching
position 1
Feedback of the cam sequencer in the converter.
p2084[8] =
r2683.8
0 = Cam switching position 1 passed
9
1 = Position actual value ≤ cam switching
position 2
p2084[9] =
r2683.9
0 = Cam switching position 2 passed
10 1 = Direct output 1 active
The converter sets these signals in the actual traversing
block.
See also paragraph: Traversing blocks (Page 205)
p2084[10] =
r2683.10
11 1 = Direct output 2 active
p2084[11] =
r2683.11
12 1 = Fixed stop reached
The axis is at the fixed stop
p2084[12] =
r2683.12
13 1 = Fixed stop clamping torque reached
The axis is at the fixed stop and has reached the clamp-
ing torque.
p2084[13] =
r2683.13
14 1 = Travel to fixed stop active
The converter moves the axis to a fixed stop.
p2084[14] =
r2683.14
15 1 = Traversing command active
Feedback signal indicating as to whether the converter
is currently moving the axis.
p2084[15] =
r2684.15
0 = Axis stationary