Adapt fieldbus configuration
6.2 PROFIdrive profile for PROFIBUS and PROFINET
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
93
6.2.1.3
Control and status word 2
Control word 2 (STW2)
Table 6- 4
Control word 2 and interconnection in the converter
Bit
Meaning
Comments
Interconnection
Telegram 9
Telegrams
110, 111
0
Drive data set selection DDS, bit 0
p0820[0] =
r2092.0
p0820[0] =
r2093.0
1
Drive data set selection DDS, bit 1
p0821[0] =
r2092.1
p0821[0] =
r2093.1
1 to 6
Reserved
7
1 = Parking axis selection
p0897 =
r2092.7
p0897 =
r2093.7
8
1 = Travel to fixed stop
p1545[0] =
r2092.8
p1545[0] =
r2093.8
9 to 15
Reserved
Status word 2 (ZSW2)
Table 6- 5
Control word 2 and interconnection in the converter
Bit
Meaning
Description
Interconnection
0
1 = Drive data set DDS effective, bit 0
p2081[0] =
r0051.0
1
1 = Drive data set DDS effective, bit 1
p2081[1] =
r0051.1
2 to 4
Reserved
---
5
1 = Alarm class bit 0
Only for internal diagnostics when using a
SIMOTION control.
p2081[5] =
r2139.11
6
1 = Alarm class bit 1
p2081[6] =
r2139.12
7
1 = Parking axis active
---
p2081[7] =
r0896.0
8
1 = Travel to fixed stop
---
p2081[8] =
r1406.8
9
Reserved
---
10
1 = Pulses enabled
Motor switched on
p2081[10] =
r0899.11
11 to 15
Reserved
---
p2081[11] =
r0835.0