Technical data
11.6 Current derating - depending on the installation altitude
Converter with control units CU250D-2
350
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
11.6
Current derating - depending on the installation altitude
Current derating depending on the installation altitude
Above 1000 m above sea level you must reduce the inverter output current as a result of the
lower cooling capability of the air.
Permissible line supplies depending on the installation altitude
●
Installation altitude up to 2000 m above sea level
–
Connection to every supply system permitted for the inverter.
●
Installation altitudes between 2000 m and 4000 m above sea level
–
Connection to a TN system with grounded neutral point.
–
TN systems with grounded line conductor are not permitted.
–
The TN line system with grounded neutral point can also be supplied using an
isolation transformer.
–
The phase-to-phase voltage does not have to be reduced.
Note
690 V Power Modules
For 690 V Power Modules, the TN line system must be established with grounded neutral
point through an isolating transformer.