Technical data
11.3 SINAMICS G120D specifications
Converter with control units CU250D-2
348
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
Feature
Specification
Brake voltage
180 V DC (400 V half-wave rectified) 1 A maximum
The UL approved current rating for the brake output is 600 mA.
Standby current
If the converter is powered-up, but the motor is still switched off, the con-
verter requires a standby current.
You have to consider the standby current when calculating the size of the
conductors and selecting the correct protective devices on the line supply.
For more comprehensive information on the standby current, please read
the following FAQ: Standby currents for PM250D
http://support.automation.siemens.com/WW/view/en/31764702
11.3
SINAMICS G120D specifications
Power Module Specifications
Table 11- 3 Power Module Frame Sizes A and B, 3 AC 380 V … 500 V, ± 10 %
Order No.
6SL3525 -
0PE17-5AA1
0PE21-5AA1
0PE23-0AA1
Output Rating (HO)
[kW]
0.75
1.5
3
Output Power
[kVA]
Rated Input Current
[A]
2.1
3.8
7.2
HO Output Current
[A]
2.2
4.1
7.7
Weight (nett)
[kg]
5.5
5.5
8.5
[lbs]
12.1
12.1
18.7
Weight (packed)
[kg]
6.5
6.5
9.5
[lbs]
14.3
14.3
20.9
Table 11- 4 Power Module Frame Sizes C, 3 AC 380 V … 500 V, ± 10 %
Order No.
6SL3525 -
0PE24-0AA1
0PE25-5AA1
0PE27-5AA1
Output Rating (HO)
[kW]
4
5.5
7.5
Output Power
[kVA]
Rated Input Current
[A]
9.5
12.2
17.7
HO Output Current
[A]
10.2
13.2
19
Weight (nett)
[kg]
9.5
9.5
9.5
[lbs]
20.9
20.9
20.9
Weight (packed)
[kg]
10.5
10.5
10.5
[lbs]
23.1
23.1
23.1