Bit Significance
Explanation
Signal inter‐
connection
in the inver‐
ter
Telegram 20
All other tele‐
grams
2
0 = Quick stop (OFF3)
Quick stop: The motor brakes with the OFF3
ramp-down time p1135 down to standstill.
p0848[0] =
r2090.2
1 = No quick stop (OFF3)
The motor can be switched on (ON command).
3
0 = Inhibit operation
Immediately switch-off motor (cancel pulses). p0852[0] =
r2090.3
1 = Enable operation
Switch-on motor (pulses can be enabled).
4
0 = Disable RFG
The inverter immediately sets its ramp-function
generator output to 0.
p1140[0] =
r2090.4
1 = Do not disable RFG
The ramp-function generator can be enabled.
5
0 = Stop RFG
The output of the ramp-function generator
stops at the actual value.
p1141[0] =
r2090.5
1 = Enable RFG
The output of the ramp-function generator fol‐
lows the setpoint.
6
0 = Inhibit setpoint
The inverter brakes the motor with the ramp-
down time p1121 of the ramp-function genera‐
tor.
p1142[0] =
r2090.6
1 = Enable setpoint
Motor accelerates with the ramp-up time p1120
to the setpoint.
7
0 → 1 = Acknowledge faults
Acknowledge fault. If the ON command is still
active, the inverter switches to"closing lockout"
state.
p2103[0] =
r2090.7
8, 9 Reserved
10 0 = No control via PLC
Inverter ignores the process data from the field‐
bus.
p0854[0] =
r2090.10
1 = Control via PLC
Control via fieldbus, inverter accepts the proc‐
ess data from the fieldbus.
11 1 = Direction reversal
Invert setpoint in the inverter.
p1113[0] =
r2090.11
12 Not used
13 ---
1)
1 = MOP up
Increase the setpoint saved in the motorized
potentiometer.
p1035[0] =
r2090.13
14 ---
1)
1 = MOP down Reduce the setpoint saved in the motorized po‐
tentiometer.
p1036[0] =
r2090.14
15 CDS bit 0
Reserved
Changes over between settings for different
operation interfaces (command data sets).
p0810 =
r2090.15
1)
If you change over from another telegram to telegram 20, then the assignment of the previous
telegram is kept.
Advanced commissioning
6.5 Drive control via PROFIBUS or PROFINET
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
183