![Siemens SINAMICS G120C Скачать руководство пользователя страница 165](http://html.mh-extra.com/html/siemens/sinamics-g120c/sinamics-g120c_operating-instructions-manual_376473165.webp)
6.3.2
Digital outputs
Changing the function of a digital output
'2
'2
'212
'2&20
'21&
%2U\\[[Q
%2U\\[[Q
S
S
To change the function of a digital output, you must in‐
terconnect the digital output with a binector output of
your choice.
Binector outputs are marked with "BO" in the parameter
list of the List Manual.
Interconnecting signals in the converter
Table 6-4
Frequently used binector outputs (BO) of the inverter
0
Deactivating digital output
r0052.08
0 signal: Deviation, setpoint/actual
speed
r0052.00
1 signal: Ready for switching on
r0052.09
1 signal: Control requested
r0052.01
1 signal: Ready for operation
r0052.10
1 signal: Maximum speed (p1082)
reached
r0052.02
1 signal: Operation enabled
r0052.11
0 signal: I, M, P limit reached
r0052.03
1 signal: Fault active
The inverter inverts signal
r0052.03 if it is interconnected to
a digital output.
r0052.13
0 signal: Alarm overtemperature motor
r0052.14
1 signal: Motor CW rotation
r0052.04
0 signal: OFF2 active
r0052.15
0 signal: Alarm inverter overload
r0052.05
0 signal: OFF3 active
r0053.00
1 signal: DC braking active
r0052.06
1 signal: Closing lockout active
r0053.02
1 signal: Speed > minimum speed
(p1080)
r0052.07
1 signal: Alarm active
r0053.06
1 signal: Speed ≥ setpoint speed (r1119)
The complete list of binector outputs is provided in the List Manual.
Overview of the manuals (Page 459)
Application example: Changing the function of a digital output
'2
U
S
To output inverter fault messages via digital output DO 1, you
must interconnect DO1 with these fault messages.
Set p0731 = 52.3
Advanced settings
You can invert the signal of the digital output using parameter p0748.
For more information, please see the parameter list and the function block diagrams 2230 f of
the List Manual.
Overview of the manuals (Page 459)
Advanced commissioning
6.3 Adapt the default setting of the terminal strip
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
165
Содержание SINAMICS G120C
Страница 2: ......
Страница 14: ...Table of contents SINAMICS G120C converter 14 Operating Instructions 09 2017 FW V4 7 SP9 A5E34263257B AF ...
Страница 469: ......