Installing
3.2 EMC-compliant installation of a machine or system
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
27
Requirements relating to shielded cables
●
Use cables with finely-stranded, braided shields.
●
Connect the shield to at least one end of the cable.
Figure 3-4
Examples for EMC-compliant shield support
●
Attach the shield to the shield support directly after the cable enters the cabinet.
●
Do not interrupt the shield.
●
Only use metallic or metallized plug connectors for shielded data cables.
3.2.3
Electromechanical components
Surge voltage protection circuit
●
Connect surge voltage protection circuits to the following components:
–
Coils of contactors
–
Relays
–
Solenoid valves
–
Motor holding brakes
●
Connect the surge voltage protection circuit directly at the coil.
●
Use RC elements or varistors for AC-operated coils and freewheeling diodes or varistors
for DC-operated coils.
Содержание SINAMICS G120
Страница 1: ...Power Module PM240 2 ...
Страница 2: ......
Страница 6: ...Preface Power Module PM240 2 4 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 10: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 116: ...Technical data 6 9 Service life Power Module PM240 2 114 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 118: ...Spare parts Power Module PM240 2 116 Hardware Installation Manual 01 2020 A5E33294624B AL ...
Страница 175: ......
Страница 176: ......