Connecting
4.4 Connecting the motor to the converter in a star or delta connection
Power Module PM240P-2
Hardware Installation Manual, 06/2020, A5E37800827C AD
47
4.4
Connecting the motor to the converter in a star or delta connection
Overview
Standard induction motors up to a rated power of approximately 3 kW are usually connected
in
star/delta connection (Y/Δ) at 400
V/230 V. For a 400-V line supply, you can connect the
motor to the converter either in a star or in a delta connection.
Function description
Operating the motor in a star connection
In a star connection, the motor can provide its
rated torque M
N
in the range 0 … rated fre-
quency f
N
.
Rated voltage U
N
= 400 V is available at a
rated frequency f
N
= 50 Hz.
The motor goes into field weakening above
the rated frequency. In field weakening, the
available motor torque decreases proportion-
ally with 1/f. In field weakening, the available
power remains constant.
Operating the motor in a delta connection with 87 Hz characteristic
In a delta connection, the motor is oper-
ated with a voltage and frequency above
its rated values. As a consequence, the
motor power is increased by a factor
√3
≈
1.73.
In the range f = 0 … 87 Hz, the motor
can output its rated torque M
N
.
The maximum voltage U = 400 V is
available at a frequency of
f =
√3
× 50
Hz ≈ 87
Hz.
The motor only goes into field weakening above 87 Hz.
The higher motor power when operated with an 87 Hz characteristic has the following
disadvantages:
●
The converter must supply approximately 1.73x current. Select a converter based on its
rated current - and not its rated power.
●
The motor temperature increases more significantly than when operated with f
≤
50 Hz.
●
The motor must have windings that are approved for a voltage > rated voltage U
N
.
●
As the fan impeller rotates faster, the motor has a higher noise level than operation with
f
≤
50 Hz.