Installing
3.3 Power losses and air cooling requirements
Power Module PM240P-2
Hardware Installation Manual, 06/2020, A5E37800827C AD
25
3.3
Power losses and air cooling requirements
Cooling requirements
To protect the components from overheating, the control cabinet requires a cooling air flow,
which depends on the power loss of the individual components.
Formula for calculating the cooling airflow:
airflow [l/s] =
power loss [W] * 0.86 / ΔT [K]
•
Power loss:
Total of the power losses of the individual components.
•
Δ T:
Permissible temperature rise in the control cabinet
Measures in order to ensure that the components are adequately cooled
•
Add the power losses of the
individual components.
–
Power Module data:
"Technical data (Page 53)".
–
The Control Unit power loss is
less than 0.04 kW.
–
Use the manufacturers data for
components, for example
reactors or filters
•
Calculate the air flow required,
using the formula above.
•
Ensure that the control cabinet is
appropriately ventilated and
equipped with suitable air filters.
•
Ensure that the components
maintain the specified clearances
with respect to one another.
•
Ensure that the components are provided with adequate cooling air through the cooling
openings.
•
Use the appropriate air barriers to prevent cooling air short circuits