Commissioning
4.7 Data backup with the operator panel and memory card
Frequency inverter
78
Operating Instructions, 08.10. 2008, t.b.d.
4.7.2
Saving and transferring data using the MMC
The MMC memory card as a medium for backing up and transferring data
You can save a parameter set on the memory card and transfer it to other frequency
inverters, e.g. to identically parameterize several devices or to transfer the settings after a
device has been replaced.
Data backup
The MMC is a removable, non-volatile flash memory for the parameter set of a frequency
inverter and does not require a power supply. For instance, this can be used to transfer
parameter settings to a new frequency inverter after the previous one was replaced.
We recommend that memory card MMC (Order No.: 6SL3254-0AM00-0AA0) should be
used.
Prerequisites for transferring data sets from the MMC to a different inverter
The Control Unit to which the parameter set is transferred must be of the same type and
have the same firmware release as the source Control Unit. (Same 'type' means: The same
Order No.)
Backup the parameters on the MMC memory card (upload)
Parameter
Description
Insert MMC
A0564
This alarm means that the MMC was inserted while the device was in operation and
that no MMC was inserted when the inverter was started.
P0003 = 3
3: Access level 3
P0010 = 30 30: Parameter transfer
P0802 = 2
2: Start data transfer from the EEPROM to the MMC. "RDY" LED flashes.
•
If the upload procedure is successful, P0010 and P0802 are set to 0 and the "RDY"
LED lights up.
•
If the download procedure is unsuccessful, F0061 or F0062 is displayed and the
LED "SF" (red) lights up. In this case, make another attempt to transfer data.
Note
Time it takes to save the data
It can take several minutes to transfer data to the MMC memory card.