Commissioning
4.7 Data backup with the operator panel and memory card
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
77
4.7
Data backup with the operator panel and memory card
4.7.1
Saving and transferring data using the BOP
The Operator Panel as a medium to backup and transfer data
You can save a parameter set on the Operator Panel and transfer it to other frequency
inverters, e.g. to identically parameterize several devices or to transfer the settings after a
device has been replaced.
Prerequisites for transferring data sets from the Operator Panel to a different inverter
The Control Unit to which the parameter set is transferred must be of the same type and
have the same firmware release as the source Control Unit. (Same 'type' means: The same
Order No.)
Saving the parameters on the Operator Panel (upload)
Parameter
Description
P0003 = 3
3: Access level 3
P0010 = 30 30: Parameter transfer
P0802 = 1
1: Start data transfer from the EEPROM to the Operator Panel.
•
If the upload procedure is successful, P0010 and P0802 are set to 0 and the "RDY"
LED lights up.
•
If the download procedure is unsuccessful, F0055 or F0057 is displayed and the
LED "SF" (red) lights up. Make another attempt to transfer the data.
Transferring parameters from the Operator Panel into the frequency inverter (download)
Parameter
Description
P0003 = 3
3: Access level 3
P0010 = 30 30: Parameter transfer
P0803 = 1
1: Starting data transfer from the BOP to the EEPROM
•
If the upload procedure is successful, P0010 and P0803 are set to 0 and the "RDY"
LED lights up.
•
If the download procedure is unsuccessful, F0055 or F0057 is displayed and the
LED "SF" (red) lights up. In this case, make another attempt to transfer data.