Commissioning
4.6 Back-up the settings and transfer
Inverter with CU240B-2 and CU240E-2 Control Units
90
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Manual download
If you do not want to switch off the power supply, then you must transfer the parameter
setting into the inverter in the following way:
Insert the memory card into the Control Unit.
The Control Unit power supply is switched-on.
E:4 S C-V3N97875
s
SINAMICS
MICRO MEMORY CARD
6SL3254-0AM00-0AA0
&8
30
STARTER
BOP-2
Set p0804 to 1.
Check the value of parameter p0804.
If data transfer has been completed, p0804 is
automatically set to 0.
Start data transfer in the menu "OPTIONS" -
"TO CRD".
Wait until the BOP-2 signals that data transfer
has been completed.
4.6.6
Safely remove the memory card
CAUTION
The file system on the memory card can be destroyed if the memory card is removed
without first requesting and confirming this using the "safe removal" function. The memory
card will then no longer function.
Procedure:
● Set p9400 to 2.
● Check the value of parameter p9400.
If it is permissible to remove the memory card, p9400 is set to 3.
● Remove the memory card.