Commissioning
4.4 Commissioning with the BOP-2
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
71
4.4.5
Basic commissioning
Table 4- 3
Set the parameters of this menu one after the other:
Menu
Remark
6(783
2.
In the BOP-2, select the menu "SETUP".
2.
5(6(7
Select Reset (Parameter p0970) if you wish to reset all parameters to the factory
setting before the basic commissioning: NO → YES → OK
Select the motor control mode:
V/f control
Vector control
VF LIN with linear characteristic
SPD N EN Speed control
…
VF QUAD with square-law
characteristic
2.
S
&75/02'
…
TRQ N EN Torque control
2.
S
(8586$
②
Standard: IEC
or NEMA
2.
S
02792/7
①
Voltage
2.
S
027&855
③
Current
2.
S
02732:
④
Power
2.
S
027530
⑥
Rated speed
2.0 HP
Y
400
460
690
V
3.55-3.55
2.05-2.05
970
970
1175
rpm
84.5%
84.5%
86.5%
0.73
0.73
0.69
PF NOM.EFF
3.15
3.5
2.05
A
kW
Hz
50
60
50
1.5
1.5
1.5
K
A
V
380 - 420
660 - 725
CL
IP55
E0807/0496382_02 003
IMB3
UNIREX-N3
40°C
Tamb
Th.Cl. 155(F)
25 kg
Design A
TEFC
MG1-12
NEMA
SF 1.15 CONT
60Hz:
Intervall: 4000hrs
IEC/EN 60034 100L
3~Mot. 1LE10011AC434AA0
6206-2ZC3
6206-2ZC3
Bearing
DE
NE
11g
15g
D-91056 Erlangen
-20°C
Motor data on the rating plate
2.
S
027,'
We recommend the setting STIL ROT (Identify motor data at standstill and with
the motor rotating).
If the motor cannot rotate freely, e.g. where travel is mechanically limited, select
the setting STILL (Identify motor data at standstill).
2.
S
&0'65&
Select the command source (terminal strip or fieldbus).
2.
S
0$,163
Select the source for the main setpoint (analog input, motorized potentiometer,
fixed setpoint or fieldbus).
2.
S
$''63
If you wish to use an additional setpoint, select the source.