Adapting the terminal strip
5.2 Digital inputs
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
86
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
5.2
Digital inputs
Digital input terminals
Changing the function of the digital input
',
',
',
',
',
',
r0722.0
r0722.1
r0722.2
r0722.3
r0722.4
r0722.5
BI: pxxxx
Interconnect the status parameter of the digital input with a
binector input of your choice.
Binector inputs are designated with "BI" in the parameter list of the
List Manual.
Table 5- 1
Binector inputs (BI) of the inverter (selection)
BI
Significance
BI
Significance
p0810 Command data set selection CDS bit 0
p1036 Motorized potentiometer, setpoint, lower
p0840 ON/OFF1
p1055 Jog bit 0
p0844 OFF2
p1056 Jog bit 1
p0848 OFF3
p1113 Setpoint inversion
p0852 Enable operation
p1201 Flying restart enable signal source
p0855 Unconditionally release holding brake
p2103 1. Acknowledge faults
p0856 Enable speed controller
p2106 External fault 1
p0858 Unconditionally close holding brake
p2112 External alarm 1
p1020 Fixed speed setpoint selection bit 0
p2200 Technology controller enable
p1021 Fixed speed setpoint selection bit 1
p3330 Two-wire/three-wire control, control
command 1
p1022 Fixed speed setpoint selection bit 2
p3331 Two-wire/three-wire control, control
command 2
p1023 Fixed speed setpoint selection bit 3
p3332 Two-wire/three-wire control, control
command 3
p1035 Motorized potentiometer, setpoint, raise
A complete list of the binector outputs is provided in the List Manual.
Table 5- 2
Examples:
',
r0722.1
722.1
p2103
Acknowledge fault with digital input 1
',
212))
r0722.2
722.2
p0840
Switch-on motor with digital input 2