Commissioning
4.5 Commissioning with STARTER
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
72
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
•
In the next step, we
recommend the setting
"Calculate motor data only".
•
①
In the next step, set the
check mark for "RAM to ROM
(save data in drive)" in order
to save your data in the
converter so that it is not lost
when the power fails.
•
②
If you exit the wizard, the
converter outputs alarm
A07791. You must now
switch-on the motor to start
motor data identification.
Switch on motor for motor data identification
CAUTION
Motor data identification for dangerous loads
Secure dangerous plant and system parts before starting the motor data identification, e.g.
by fencing off the dangerous location or lowering a suspended load to the floor.