Appendix
A.1 Application examples
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
324
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
In order to configure the communication you also require the following software packages:
Table A- 2
Software components
Component
Type (or higher)
Order no.
Qty
SIMATIC STEP 7
V5.3 + SP3
6ES7810-4CC07-0YA5
1
STARTER
V4.2
6SL3072-0AA00-0AG0
1
A.1.1.3
Creating a STEP 7 project
PROFIBUS communication between the inverter and a SIMATIC control is configured using
the SIMATIC STEP 7 and HW Config software tools.
Procedure
●
Create a new STEP 7 project and assign a project name, e.g. "G120_in_S7". Add an S7
300 CPU.
Figure A-1
Inserting a SIMATIC 300 station into a STEP 7 project
●
Select the SIMATIC 300 station in your project and open the hardware configuration (HW
Config) by double clicking on "Hardware".
●
Add an S7 300 mounting rail to your project by dragging and dropping it from the
"SIMATIC 300" hardware catalog. Locate a power supply at slot 1 of the mounting rail
and a CPU 315-2 DP at slot 2.