7.4 Setpoint sources
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
200
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
Example: Selecting two fixed speed setpoints using digital input 2 and digital input 3
The motor is to run at two different speeds:
●
The motor is switched on with digital input 0
●
When digital input 2 is selected, the motor is to run at a speed of 300 rpm.
●
When digital input 3 is selected, the motor is to accelerate to a speed of 2000 rpm.
●
When digital input 1 is selected, the motor should go into reverse
Table 7- 21 Parameter settings for the example
Parameter
Description
p0015 = 12
Macro drive unit: Configure inverter with terminal strip as the command
and setpoint source.
•
The motor is switched on and off via digital input 0.
•
The setpoint source is analog input 0.
p1001 = 300.000
Defines the fixed setpoint 1 in [rpm]
p1002 = 2000.000
Defines the fixed setpoint 2 in [rpm]
p1016 = 1
Direct selection of fixed setpoints
p1020 = 722.2
Interconnection of fixed setpoint 2 with DI 2.
r0722.2 = parameter that displays the status of digital input 2.
p1021 = 722.3
Interconnection of fixed setpoint 3 with status of DI 3.
r0722.3 = parameter that displays the status of digital input 3.
p1070 = 1024
Interconnect main setpoint with fixed speed setpoint
7.4.4
Running the motor in jog mode (JOG function)
Using the "jog" function (JOG function), you can switch the motor on and off using a control
command or the operator panel. The speed to which the motor accelerates for "Jog" can be
set.
The motor must be switched-off before you issue the "jog" control command. "Jog" has no
effect when the motor is switched on.
The "Jog" function is typically used to manually switch-on a motor after switching over from
automatic to manual operation.
Setting jogging
The "Jog" function has two different speed setpoints, e.g. for motor counter-clockwise
rotation and clockwise rotation.
With an operator panel, you can always select the "Jog" function. If you wish to use
additional digital inputs as control commands, you must interconnect the particular signal
source with a digital input.