Configuring the fieldbus
6.3 Communication over CANopen
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
178
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
6.3.4.2
Objects in drive profile DSP402
The following table lists the object directory with the index of the individual objects for the
drives.
Table 6- 53 Objects in drive profile DSP402
OD index
(hex)
Sub-
index
(hex)
Name of the object
SINAMICS
parameters
Transmissio
n
Data type
Default
setting
Can be
read/
written
to
Predefinitions
67FF
Single device type
SDO
Unsigned32
R
Common entries in the object dictionary
6007
Abort connection option code p8641
SDO
Integer16
3
R/W
6502
Supported drive modes
SDO
Integer32
R
6504
Drive manufacturer
SDO
String
SIEMENS
R
Device control
6040
Control word
r8795
PDO/SDO Unsigned16
–
R/W
1)
6041
Status word
r8784
PDO/SDO Unsigned16
–
R
6060
Modes of operation
p1300
SDO
Integer8
–
R/
2)
6061
Modes of operation display
p1300
SDO
Integer8
–
R
Profile torque mode
6071
Target torque
Set torque
p1513[0]
SDO/PDO Integer16
–
R/W
1)
6072
Max. torque
p1520/p1521 SDO
Real32
-
R/W
6074
Torque demand value
Actual torque
r0080
SDO/PDO Integer16
–
R
Velocity mode
6042
0
vl target velocity
r0060
SDO/PDO Integer16
-
R/W
6044
0
vl control effort
r0063
SDO/PDO Integer16
-
R
1) SDO access is only possible after mapping the objects and the BICO interconnection to
display parameters.
2) Object cannot be written to as a CANopen device profile is not supported, only
manufacturer-specific operating data