Configuring the fieldbus
6.3 Communication over CANopen
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
170
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
6.3.4
Object directories
RPDO configuration objects
The following tables list the communication and mapping parameters together with the
indices for the individual RPDO configuration objects. The configuration objects are
established via SDO.
Table 6- 49 RPDO configuration objects - communication parameters
OD
Index
(hex)
Sub-
Index
(hex)
Name of the object
SINAMICS
parameters
Data type
Predefined
connection set
Can be
read/
written to
1400
Receive PDO 1 communication parameter
0
Largest subindex supported
Unsigned8
2
R
1
COB ID used by PDO
p8700.0
Unsigned32 200 hex + node ID
R/W
2
Transmission type
p8700.1
Unsigned8
FE hex
R/W
1401
Receive PDO 2 communication parameter
0
Largest subindex supported
Unsigned8
2
R
1
COB ID used by PDO
p8701.0
Unsigned32 300 hex + node ID
R/W
2
Transmission type
p8701.1
Unsigned8
FE hex
R/W
1402
Receive PDO 3 communication parameter
0
Largest subindex supported
Unsigned8
2
R
1
COB ID used by PDO
p8702.0
Unsigned32 8000 06DF hex
R/W
2
Transmission type
p8702.1
Unsigned8
FE hex
R/W
1403
Receive PDO 4 communication parameter
0
Largest subindex supported
Unsigned8
2
R
1
COB ID used by PDO
p8703.0
Unsigned32 8000 06DF hex
R/W
2
Transmission type
p8703.1
Unsigned8
FE hex
R/W
1404
Receive PDO 5 communication parameter
0
Largest subindex supported
Unsigned8
2
R
1
COB ID used by PDO
p8704.0
Unsigned32 8000 06DF hex
R/W
2
Transmission type
p8704.1
Unsigned8
FE hex
R/W
1405
Receive PDO 6 communication parameter
0
Largest subindex supported
Unsigned8
2
R
1
COB ID used by PDO
p8705.0
Unsigned32 8000 06DF hex
R/W
2
Transmission type
p8705.1
Unsigned8
FE hex
R/W
1406
Receive PDO 7 communication parameter
0
Largest subindex supported
Unsigned8
2
R
1
COB ID used by PDO
p8706.0
Unsigned32 8000 06DF hex
R/W
2
Transmission type
p8706.1
Unsigned8
FE hex
R/W