AS-i System Interface Manual (
https://support.industry.siemens.com/cs/gb/en/view/
)
Table 4-9
Pin assignment
X03 AS-i (M12)
Pin
Function
Description
1
AS-i +
AS-i plus signal
2
0 V
Reference potential for terminal 4
3
AS-i -
AS-i minus signal
4
24 V
24 V auxiliary voltage
5
Not assigned
4.4.4.1
Setting the address
As factory setting, all AS-i slaves have address 0. Slaves with address 0 are not included in the
communication.
The addresses must be unique, although they can be mixed as required.
You have the following options when making the address assignment:
• Automatic addressing via the AS-i master
• Addressing via the addressing device
• Addressing via parameters
Before you set the address, you must specify whether the converter is integrated as Single Slave
or Dual Slave in the AS-i network.
• p2013 = 0: Single Slave (factory setting)
• p2013 = 2: Dual Slave
If for the commissioning you select the default setting 30 or 32 (Single Slave), or 31 or 34 (Dual
Slave), p2013 is assigned the appropriate value.
Note
Changes made to p2012 and p2013
Changes made to the p2012 and p2013 parameters take effect immediately after the change.
If you work with Startdrive, you must back up the changes so they are not lost when the system
is switched off and on again.
Automatic addressing via the AS-i master
Single Slave
For automatic addressing, the address is specified by the AS-i master. For a Single Slave, the
master checks which slave has address 0 and assigns it the next free address. This address is also
written to parameter p2012. If more than one slave has address 0, an automatic addressing is
not possible.
Installation
4.4 Connecting the converter to the fieldbus
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
95
Содержание SINAMICS G110M
Страница 2: ......
Страница 426: ...Index Distributed converter for SIMOGEAR geared motors 424 Operating Instructions 10 2020 FW V4 7 SP13 A5E31298649B AL ...
Страница 427: ......