You have now installed the GSD file in the engineering system of the controller.
4.4.3.4
Set the PROFIBUS address
Valid address area: 1 … 125
You have the following options for setting the address:
• Using the address switch on the Control Unit:
([DPSOH
2II
%LW
%LW
%LW
%LW
%LW
%LW
%LW
2II
2Q
2Q
Figure 4-36
Address switch with example for bus address 10
The address switch has priority over the other settings.
• With a commissioning tool, e.g. an operator panel, via parameter p0918 (factory setting:
p0918 = 126).
It is only possible to change p0918 if an invalid address is set in the address switch.
General layout SINAMICS G110M system (Page 29)
Setting the bus address
Procedure
1. Set the address using one of the subsequently listed options:
– Via the address switch
– With a commissioning tool via p0918
2. Switch off the converter power supply.
3. Wait until all LEDs on the converter are dark.
4. Switch on the converter power supply again.
Your settings become effective after switching on.
The PROFIBUS address is set.
❒
Installation
4.4 Connecting the converter to the fieldbus
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL