4.2
System Installation
4.2.1
Overview
Description
The SINAMICS G110M is generally delivered as a complete system with the following
components:
• Power Module
• Terminal Housing including the Control Module
• Motor or geared motor
If the SINAMICS G110M is delivered as a complete system, then it is delivered totally assembled
and all that is required is the external wiring of the system.
It is also possible that the SINAMICS G110M system is delivered as separate components, which
will require the system to be fitted together before installation and commissioning can take
place.
To perform the complete assembly of the system, the procedures in the following sections
should be performed.
DANGER
Electrical shock due to unexpected voltages
When the converter and motor are powered-up, high voltages are present in the electrical
components of the system, any contact with these components could result in severe personal
injury or death.
• Don't apply the mains supply and external power sources to the system during the
installation procedure.
NOTICE
Overheating the converter by the braking resistor
The internal braking resistor, when used, generates a large amount of heat. This heat has the
potential to overheat the Communications and Power Interface.
• Fit the internal braking resistor on the opposite side of the Terminal Housing from the
Communications and Power Interface.
Installation
4.2 System Installation
Distributed converter for SIMOGEAR geared motors
42