EMC Emissions
Table A-10
Conducted disturbance voltage and radiated emissions
EMC Phenomenon
Converter type
Remark
Level acc. to
IEC 61800‑3
Conducted emissions
(disturbance voltage)
All converters with integrated class A filters.
Article number:
6SL3517-1BE**-*A**
Category C2
First Environment -
Professional Use
Radiated emissions
Converter frame sizes A and B with integrated class A
filter.
Article number:
6SL3517-1BE11-*A*0
6SL3517-1BE12-*A*0
6SL3517-1BE13-*A*0
6SL3517-1BE14-*A*0
6SL3517-1BE16-*A*0
6SL3517-1BE17-*A*0
6SL3517-1BE21-*A*0
In a domestic environment this product may cause radio
interference in which case supplementary mitigation
measures may be required.
Category C2
First Environment -
Professional Use
Caution
In a residential environment, this product may cause radio interference, in which case
supplementary mitigation measures may be required.
Harmonic Currents
Table A-11
Harmonic Currents
Typical Harmonic Current (% of rated input current) at U
K
1 %
5th
7th
11th
13th
17th
19th
23rd
25th
24
11
9
7
6
5
4
4
Note
Units installed within the category C2 (domestic) environment require supply authority
acceptance for connection to the public low-voltage power supply network. Please contact your
local supply network provider.
Units installed within the category C3 (industrial) environment do not require connection
approval.