Binectors and connectors
Connectors and binectors are used to exchange signals between the individual blocks:
• Connectors are used to interconnect "analog" signals (e.g. MOP output speed)
• Binectors are used to interconnect digital signals (e.g. "Enable MOP up" command)
%,&2EORFN
%LQHFWRULQSXW
%LQHFWRURXWSXW
%LQHFWRUFRQQHFWRURXWSXW
&RQQHFWRURXWSXW
&RQQHFWRULQSXW
S[[[[
U[[[[
U[[[[
U[[[[
U[[[[
S[[[[
%,
&2
%2
&2%2
&,
Figure A-3
Symbols for binector and connector inputs and outputs
Binector/connector outputs (CO/BO) are parameters that combine more than one binector
output in a single word (e.g. r0052 CO/BO: status word 1). Each bit in the word represents a
digital (binary) signal. This summary reduces the number of parameters and simplifies
parameter assignment.
Binector or connector outputs (CO, BO or CO/BO) can be used more than once.
Interconnecting signals
When must you interconnect signals in the converter?
If you change the signal interconnection in the converter, you can adapt the converter to a wide
range of requirements. This does not necessarily have to involve highly complex functions.
Example 1: Assign a different function to a digital input.
Example 2: Switch the speed setpoint from the fixed speed to the analog input.
Principle when connecting BICO blocks using BICO technology
When interconnecting the signal, the following principle applies: Where does the signal come
from?
An interconnection between two BICO blocks consists of a connector or a binector and a BICO
parameter. The input of a block must be assigned the output of a different block: In the BICO
parameters, enter the parameter numbers of the connector/binector that should supply its
output signal to the BICO parameter.
How much care is required when you change the signal interconnection?
Note which changes you make. A subsequent analysis of the set signal interconnections is
possible only by evaluating the parameter list.
Where can you find additional information?
• All the binectors and connectors are located in the Parameter list.
• The function diagrams provide a complete overview of the factory setting for the signal
interconnections and the setting options.
Appendix
A.2 Interconnecting signals in the converter
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
409