11.Mount the Power Module.
9
5'<
12.Switch on the 24 V converter power supply voltage or the 400 V converter supply.
13.If the firmware upgrade was successful, the converter LED RDY turns green after several
seconds.
You have successfully updated the converter's firmware to a newer version.
❒
When there is an upgrade, your settings will be stored in the converter.
10.4.2
Firmware downgrade
When downgrading firmware you replace the converter's firmware with an older version. Only
update the firmware to an older level if, after replacing a converter, you require the same
firmware in all converters.
Requirements
• Your converter's firmware is at least version V4.7.
• You have the memory card with the firmware for that particular converter.
• You have saved your settings onto a memory card, in an operator panel or on a PC.
Corrective maintenance
10.4 Firmware upgrade and downgrade
Distributed converter for SIMOGEAR geared motors
382
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL