10.2
Downloading the converter settings
10.2.1
Converter without enabled safety functions
10.2.1.1
Automatic download from the memory card
Overview
We recommend that you insert the memory card before switching on the converter. The
converter automatically imports its settings from the inserted memory card.
Precondition
The following requirements apply:
• The converter power supply has been switched off.
• The converter settings are not protected against copying.
Download with active know-how protection with copy protection (Page 375)
Function description
Procedure
1. Insert the memory card into the converter.
2. Switch on the power supply for the converter.
3. The converter loads the settings from the memory card.
4. After loading, check whether the converter outputs Alarm A01028.
– Alarm A01028:
The loaded settings are not compatible with the converter.
Delete the alarm with p0971 = 1.
Recommission the drive.
– No alarm A01028:
The converter accepts the settings that have been loaded.
You have transferred the settings to the converter.
❒
10.2.1.2
Manual download from the memory card using Startdrive
Overview
If you have backed up the settings of several converters on the memory card, the settings
download must be started manually.
Corrective maintenance
10.2 Downloading the converter settings
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL