
8.22
Converter protection using temperature monitoring
Overview
The converter temperature is essentially defined by the following effects:
• The ambient temperature
• The ohmic losses increasing with the output current
• Switching losses increasing with the pulse frequency
Monitoring types
The converter monitors its temperature using the following monitoring types:
• I
2
t monitoring (alarm A07805, fault F30005)
• Measuring the chip temperature of the Power Module (alarm A05006, fault F30024)
• Measuring the heat sink temperature of the Power Module (alarm A05000, fault F30004)
Function description
Overload response for p0290 = 0
The converter responds depending on the control mode that has been set:
• In vector control, the converter reduces the output current.
• In U/f control, the converter reduces the speed.
Once the overload condition has been removed, the converter re-enables the output current or
speed.
If the measure cannot prevent a converter thermal overload, then the converter switches off the
motor with fault F30024.
Overload response for p0290 = 1
The converter immediately switches off the motor with fault F30024.
Overload response for p0290 = 2
We recommend this setting for drives with square-law torque characteristic, e.g. fans.
Advanced commissioning
8.22 Converter protection using temperature monitoring
Distributed converter for SIMOGEAR geared motors
320
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Содержание SINAMICS G110M
Страница 2: ......
Страница 426: ...Index Distributed converter for SIMOGEAR geared motors 424 Operating Instructions 10 2020 FW V4 7 SP13 A5E31298649B AL ...
Страница 427: ......