8.7.3
Assignment tables
Fixed speeds - Single Slave
Table 8-33
Fixed speeds via the motor control bits
AS-i.DO3
AS-i.DO2
AS-i.DO1
AS-i.DO0 Response in the converter
0
0
0
0
OFF1
0
0
0
1
On + fixed speed 1 (factory setting: 1500 rpm)
0
0
1
0
On + fixed speed 2 (factory setting: -1500 rpm)
0
0
1
1
On + fixed speed 3 (factory setting: 300 rpm)
0
1
0
0
On + fixed speed 4 (factory setting: 450 rpm)
0
1
0
1
On + fixed speed 5 (factory setting: 600 rpm)
0
1
1
0
On + fixed speed 6 (factory setting: 750 rpm)
0
1
1
1
On + fixed speed 7 (factory setting: 900 rpm)
1
0
0
0
On + fixed speed 8 (factory setting: 1050 rpm)
1
0
0
1
On + fixed speed 9 (factory setting: 1200 rpm)
1
0
1
0
On + fixed speed 10 (factory setting: 1350 rpm)
1
0
1
1
On + fixed speed 11 (factory setting: 1500 rpm)
1
1
0
0
On + fixed speed 12 (factory setting: 1650 rpm)
1
1
0
1
On + fixed speed 13 (factory setting: 1800 rpm)
1
1
1
0
On + fixed speed 14 (factory setting: 1950 rpm)
1
1
1
1
Acknowledge fault or OFF2
Modified addressing - scaling factors
Table 8-34
Scaling of the speed setpoint via AS-i.P0 … AS-i.P3
AS-i.P3
AS-i.P2
AS-i.P1
AS-i.P0
Scaling factor
Frequency (Hz)
1
1
1
1
1
50
1
1
1
0
0.9
45
1
1
0
1
0.8
40
1
1
0
0
0.7
35
1
0
1
1
0.6
30
1
0
1
0
0.5
25
1
0
0
1
0.45
22.5
1
0
0
0
0.4
20
0
1
1
1
0.35
17.5
0
1
1
0
0.3
15
0
1
0
1
0.25
12.5
0
1
0
0
0.2
10
0
0
1
1
0.15
7.5
0
0
1
0
0.1
5
Advanced commissioning
8.7 Control via AS-i
Distributed converter for SIMOGEAR geared motors
212
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL
Содержание SINAMICS G110M
Страница 2: ......
Страница 426: ...Index Distributed converter for SIMOGEAR geared motors 424 Operating Instructions 10 2020 FW V4 7 SP13 A5E31298649B AL ...
Страница 427: ......