8.6.6
Parameter channel
Overview
The parameter channel allows parameter values to be cyclically read and written to.
6XELQGH[
3DJHLQGH[
3.(VWZRUG
3DUDPHWHUFKDQQHO
3:(UGDQGWKZRUGV
,1'QGZRUG
3:(
3:(
$.
318
6
3
0
Structure of the parameter channel:
• PKE (1st word)
– Type of task (read or write).
– Bit 11 is reserved and is always assigned 0.
– Parameter number
• IND (2nd word)
– Parameter index
• PWE (3rd and 4th word)
– Parameter value
Function description
AK: Request and response ID
Table 8-24
Request identifiers, control → converter
AK
Description
Response identifier
positive
nega‐
tive
0
No request
0
7 / 8
1
Request parameter value
1 / 2
7 / 8
2
Change parameter value (word)
1
7 / 8
3
Change parameter value (double word)
2
7 / 8
4
Request descriptive element
1)
3
7 / 8
6
2)
Request parameter value (field)
1)
4 / 5
7 / 8
7
2)
Change parameter value (field, word)
1)
4
7 / 8
8
2)
Change parameter value (field, double word)
1)
5
7 / 8
9
Request number of field elements
6
7 / 8
1)
The required element of the parameter is specified in IND (2nd word).
2)
The following request IDs are identical: 1 ≡ 6, 2 ≡ 7 and 3 ≡ 8.
We recommend that you use identifiers 6, 7 and 8.
Advanced commissioning
8.6 Drive control via PROFIBUS or PROFINET
Distributed converter for SIMOGEAR geared motors
194
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL