8.5.3
Two-wire control, clockwise/counterclockwise rotation 2
Function description
&ORFNZLVH
&RXQWHUFORFNZLVH
212))
&RXQWHUFORFNZLVH
212))
&ORFNZLVH
6SHHGVHWSRLQW
W
W
W
6723
6723
6723
Figure 8-7
Two-wire control, clockwise/counterclockwise rotation 2
Commands "ON/OFF1 clockwise rotation" and "ON/OFF1 counter-clockwise rotation" switch on
the motor - and simultaneously select a direction of rotation. The converter accepts a new
command at any time, independent of the motor speed.
Table 8-14
Function table
ON/OFF1 clockwise rota‐
tion
ON/OFF1 counter-clock‐
wise rotation
Function
0
0
The motor stops.
1
0
Clockwise motor rotation.
0
1
Counter-clockwise motor rotation.
1
1
The motor stops.
Examples
Table 8-15
Two-wire control and setting the assignment of the digital inputs
Parameter
Description
p3334 = 2
2/3 wire control selection
2: Two-wire control, clockwise/counterclockwise rotation 2
p3330[C] = 722.0
BI: 2/3 wire control command 1 (ON/OFF1 clockwise rotation)
Command is received via digital input 0 (DI 0)
p3331[C] = 722.1
BI: 2/3 wire control command 2 (ON/OFF1 counter-clockwise rotation)
Command is received via digital input 1 (DI 1)
Advanced commissioning
8.5 Controlling clockwise and counter-clockwise rotation via digital inputs
Distributed converter for SIMOGEAR geared motors