2 Parameters
2.2 List of parameters
SINAMICS DCP
22
List Manual (LH21), 05/2016
2.2
List of parameters
Product: SINAMICS DCP, Version: 4703500, Language: eng
Objects: CU_DCP, DCP_CTRL, TM150, TM15DI_DO, TM31
Product: SINAMICS DCDC_V, Version: 1200700, Language: eng
Objects: DCP_CTRL
Description:
Operating display for the Control Unit (CU).
Value:
0:
Operation
10:
Ready
20:
Wait for run-up
25:
Wait for automatic FW update of DRIVE-CLiQ components
31:
Commissioning software download active
33:
Remove/acknowledge topology error
34:
Exit commissioning mode
35:
Carry out first commissioning
70:
Initialization
80:
Reset active
99:
Internal software error
Notice:
For several missing enable signals, the corresponding value with the highest number is displayed.
Description:
Operating display for the drive.
Value:
0:
o0.0 No torque direction switched on
1:
o0.1 Torque direction I switched on
12:
o1.2 Wait for operating enable (signal source acc. to p0852)
16:
o1.6 Wait for withdrawal of the immediate pulse inhibit
31:
o3.1 Wait for line supply symmetry
40:
o4.0 Wait for voltage at 1U1, 1V1, 1W1
41:
o4.1 Wait until fuse monitoring signals OK
71:
o7.1 Wait for power-on (signal source according to p0840)
80:
o8.0 Switching on inhibited
81:
o8.1 Simulation mode active
91:
o9.1 Quick stop (OFF3) (signal source acc. to p0848) present
92:
o9.2 Quick stop (OFF3) (signal source acc. to p0849) present
101:
o10.1 Voltage disconnect (OFF2) (signal source acc. to p0844)
102:
o10.2 Voltage disconnect (OFF2) (signal source acc. to p0845)
103:
o10.3 E stop (safety shutdown) (terminal 105/106)
110:
o11.0 Fault present
121:
o12.1 Initializ. of line voltage sensing for armature in progr.
123:
o12.3 Reading out data of the gating modules
124:
o12.4 Offset calibr. of curr. act. val. sensing being performed
125:
o12.5 Read out data from the power unit
126:
o12.6 Initializing the second processor (TMS320)
Notice:
For several missing enable signals, the corresponding value with the highest number is displayed.
Note:
OC: Operating condition
RFG: Ramp-function generator
COMM: Commissioning
r0002
Control Unit operating display / CU op_display
CU_DCP
Can be changed:
-
Access level:
1
Data type:
Integer16
Func. diagram:
2651
Min Max
Factory
setting
0 99
-
r0002
Drive operating display / Drv op_display
DCP_CTRL
Can be changed:
-
Access level:
1
Data type:
Integer16
Func. diagram:
2651
Min Max
Factory
setting
0 126
-
Содержание sinamics dcp
Страница 1: ...s SINAMICS drives SINAMICS DCP DC DC Power Converter List Manual 05 2016 Edition Siemens Parts ...
Страница 2: ......
Страница 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Страница 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Страница 12: ...1 Fundamental safety instructions 1 2 Industrial security SINAMICS DCP 12 List Manual LH21 05 2016 ...
Страница 380: ...3 Function diagrams 3 14 Basic Operator Panel 20 BOP20 SINAMICS DCP 380 List Manual LH21 05 2016 ...
Страница 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Страница 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Страница 517: ...Siemens Parts ...