Supplementary system components
6.5 CX32-2 controller extension
SIMOTION D4x5-2
118
Manual, 02/2012
6.5.2.3
DRIVE-CLiQ interface
Table 6- 21 DRIVE-CLiQ interface X100 – X103
Pin
Signal name
Technical specifications
1
TXP
Transmit data +
2
TXN
Transmit data -
3
RXP
Receive data +
4
Reserved, do not use
5
Reserved, do not use
6
RXN
Receive data -
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
Power supply
B
M (0 V)
Electronic ground
Dust protection blanking plugs for sealing unused DRIVE-CLiQ ports:
•
Three blanking plugs contained in the CX32-2 scope of delivery
•
Blanking plugs (50 pcs) order number: 6SL3066-4CA00-0AA0
6.5.2.4
Digital I/Os (X122)
Interface characteristics
Sensors and actuators can be connected to the X122 connector via digital inputs and
outputs.
Table 6- 22 X122 wiring
Characteristics
Type
Connector type
Mini Combicon
Connectable cable types:
- Rigid
- Flexible
- Flexible, with end sleeve without plastic sleeve
- AWG/kcmil
Conductor cross-sections:
0.2 mm
2
to 1 mm
2
0.2 mm
2
to 1.5 mm
2
0.25 mm
2
to 1.5 mm
2
24 to 16
Stripped length
8 mm
Tool
Screwdriver 0.4 x 2.0 mm
Max. cable length
30 m
Max. current carrying capacity (ground)
6 A
Содержание SIMOTION TB30
Страница 10: ...Table of contents SIMOTION D4x5 2 10 Manual 02 2012 ...
Страница 36: ...Description 1 9 CompactFlash card SIMOTION D4x5 2 36 Manual 02 2012 ...
Страница 46: ...Operator control hardware 2 3 7 segment and LED displays SIMOTION D4x5 2 46 Manual 02 2012 ...
Страница 72: ...Interfaces 3 10 USB interfaces SIMOTION D4x5 2 72 Manual 02 2012 ...
Страница 134: ...Supplementary system components 6 11 DMC20 DRIVE CLiQ hub SIMOTION D4x5 2 134 Manual 02 2012 ...
Страница 142: ...Standards and approvals A 3 Safety of electronic controllers SIMOTION D4x5 2 142 Manual 02 2012 ...
Страница 150: ...Index SIMOTION D4x5 2 150 Manual 02 2012 ...