P86 Trolley damping factor when accelerating (MAN)
Trolley damping factor for conventional sway control in manual (MAN) mode when
accelerating. High values result in non-periodic transient responses and low values in
overshoots and shorter rise times. To achieve fast acceleration, the value should be lower than
the deceleration setting.
Default: 0.9
min: 0
max: 2.5
Access code: 2
Display: Always
P87 Factor for reduction of overshoot when stopping trolley
The parameter is operative in the POS, SNL, SND and SAM modes, and prevents overshoot
during sway controlled stopping. If values are > 0, the overshoot is reduced. If P87 = 0, it has
no effect.
Default: 1.3
min: 0
max: 2.5
Access code: 1
Display: Always
P88 Trolley damping factor when decelerating in SAM, POS, SNL, SND
Damping factor for conventional sway control when decelerating in modes SAM, POS, SNL,
SND. High values result in non-periodic transient responses and low values in overshoots and
shorter rise times.
Default: 1.1
min: 0
max: 2.5
Access code: 2
Display: Always
P89 Trolley damping factor when accelerating in SAM, POS, SNL, SND
Damping factor for conventional sway control when accelerating in modes SAM, POS, SNL,
SND. High values result in non-periodic transient responses and low values in overshoots and
shorter rise times. To achieve fast acceleration, the value should be lower than the deceleration
setting.
Default: 0.9
min: 0
max: 2.5
Access code: 2
Display: Always